ClassiCAFS

Robwen Inc. has gained worldwide reputation as a recognized leader in the manufacture of foam generating equipment. From the longstanding bladder systems to the more recent Hydro-Flo series to our line of aspirating nozzles, water pumps and slip-on foam systems, Robwen has always endeavored to offer quality, dependable products at a reasonable price and to back the sales effort with unmatched customer service.

The industry trend in recent years has been a move towards the use of compressed air form systems (CAFS). Given our family of products, it seemed natural to bring these components together to produce a CAFS of our own. We are pleased to introduce you to ClassiCAFS by Robwen. consulting with some of the most experienced CAFS engineers in the industry, we have built ClassiCAFS around the HF100 and our model 180 pump.

 

ClassiCAFS II

1. General
CLASSIC CAFS provides a "self-contained" gas powered "modular" Compressed Air Foam System (CAFS). The CAFS module shall be designed for slip-on or quick attack applications.

The CAFS shall be designed to discharge water only, air only, foam solution only or compressed air foam solution. In addition, the consistency of the compressed air foam (expansion ratio) shall be fully adjustable and repeatable. See sections 7A and 7B.

2. Capacities and Dimensions
A. Weight Apx. 750 Lbs.
B. Dimensions 5" H 50" D 48"W
C. Water Pump Capacity, Minimum 100 GPM
D. Air compressor Capacity, Minimum 50 cu. ft.
E. Simultaneous Flows 80 GPM + 50 CFM @ 100 PSI
F. Maximum Water PSI at 3600 250 PSI
G. Engine Horsepower 36 HP (two 18 HP)

3. Engines
The engines shall be Briggs & Stratton, 2 Cylinder, 4 Cycle gas developing 18 horsepower each at 3600 RPM, air-cooled, 23 amp alternators, 12 volt electric start, dry cartridge air filters and mufflers.

4. Water Pump
The water pump shall be a Robwen model 180, with the following features; aluminum casing, bronze impeller and stainless steel wear rings, impeller shaft, mechanical seal.

5. Drive System
The water pump and air compressor are belt driven off the engine crankshafts. They shall be driven via a toothed belt. The complete drive system shall have a 2,000 hour rated service life and it shall be designed and rated for the imposed speed and load. Belt guards are provided.

6. Pump Primer

Forest Service approved diaphragm style water pump primer. Includes primer ON/OFF valve. .

7. Air Compressor

The air compressor shall be of the oil flooded rotary screw type, designed and installed to supply a minimum of 50 CFM / 125 psi of free air at maximum engine RPM. The compressor sump shall be built and designed by the compressor manufacturer. A spin-on oil filter shall also be integrated into the compressor system. Replacement elements shall be readily available.

The air compressor shall be driven via a dry Poly chain drive from the engine crankshaft and will be mounted to the pump platform. The compressor drive ratio shall allow operation of the air end at maximum RPM while the water pump is developing 120 to 130 PSI in a "no-flow" state. The air compressor shall be capable of maintaining prolonged pressure from 100 to 150 pounds per square inch throughout the service life of the complete CAFS unit.

The compressor shall be controlled by a pneumatic modulating inlet valve mounted to the air end inlet. This controller shall sense air pressure and control the air delivery of the air end while maintaining constant pressure. An automatic balancing system shall be provided to automatically maintain the air pressure within plus-or-minus 5% of the water pump pressure throughout the CAFS operating range.
The air compressor shall be cooled by the units water pump, using a shell and tube heat exchanger of all brass and copper construction. Water shall flow through the heat exchanger whenever the water pump is operating. The air compressor cooling system shall incorporate a thermostat that maintains the system oil temperature within a 168 to 225 degree range. The system shall be capable of maintaining recommended operating temperatures throughout the full operational range in ambient temperatures up to 115 degrees. A dry cartridge type air filter shall be provided on the compressor air intakes.


7A. CAFS Air Metering Valve
System shall have an air metering valve incorporating 20 CFM, 35 CFM and 50 CFM flow settings.

7B. CAFS Solution Metering Valve
System shall have a solution metering valve incorporating 10 GPM, 20 GPM, 40 GPM and 80 GPM flow settings.

8. Compressed Air Delivery

All air lines shall be rated to a minimum of 250 PSI. All air line fittings shall be of brass or bronze construction. Stainless steel or brass check valves shall be utilized at air injection points to prevent water/solution back-flow into air lines. Compressed air shall be injected into CAFS solution untilizing the patented Robwen Check-Vent air injection valve.

9. Discharge Plumbing

All foam plumbing to be brass 1 ½" pipe. A brass spring-loaded check valve shall be installed on foam discharge to prevent air back-flow into the foam pump. Foam mix valve is to be 1 ½ Legend. Water discharge valve is to be Bronze alloy 1 - piece 1 ½" NST-m Legend valve.

10. Skid Frame

An aluminum welded frame shall be provided to support the entire slide-in module, with the base constructed of 3/8" aluminum plate. The frame shall be strong enough to support the weight of the pumping equipment while in the apparatus and during loading and unloading and shall be utilized as a base mount for the engine, compressor and pump. The frame will have fork lift access openings.

11. Foam Proportioner

A Robwen 500 B Proportioner shall be provided and installed to inject foam concentrate into the discharge plumbing. The proportioner shall automatically meter the correct percentage of foam concentrate, based on current flow, into the water stream. An integral check valve shall be provided upstream of the foam injection point to prevent foam solution back-flow. No electrical power is required other than the refill pump. Proportioner on/off, ratio controls, operating instructions shall be mounted on the pump panel. (The optional A & B 1% foam system quoted upon request.)

12. Electrical System
All electrical equipment installed by the manufacturer shall conform to current automotive electrical system standards and the requirements of the applicable NFPA, Apparatus Standard. Wiring shall be individually and permanently color and function coded. The installation shall meet SAE Standard J1128 in its latest edition for GXL or SXL temperature rating.

All exposed wiring shall run in loom with a minimum 280 degree rating. All wiring loom shall be properly supported and attached to frame members along the entire run. At any point where wire or looms must pass through metal, rubber grommets shall be installed to protect the wire from abrasion.

The main low voltage electrical terminal block and circuit breaker panel shall be provided behind the pump operator's panel in a location providing easy service access. An electrical quick disconnect shall be provided for connection to the chassis electrical system or battery with hold tray.

Electrical connection shall be made using heat shrink and/or weatherproof connectors. All electrical circuits shall be protected with automatic reset circuit breakers.


13. Pump Panel

The pump panel shall be constructed of powder coated aluminum attached with stainless steel machine screws to the unit frame. The following controls and instruments shall be provided on the panel:
Shielded pump panel light cluster and switch
2 ½" Master pump pressure gauge,
2 ½" Master air pressure gauge
Air compressor temperature switch gauge and 97 decibel overheat alarm
Instructional plate
Ignition switchs
Engine chokes
Cable throttle controls
Proportioner controls with instruction plate
Water only discharge - 1 ½" NST - M., chromed .
Foam discharge outlet - 1 ½" NST - M. ,chromed, controlled at the panel.
The compressed air discharge shall be control color coded and located next to respective water control.
Diaphragm primer system for water pump
Pump drain, bladder tank drain, heat exchanger drain
Mechanically attached color coded and engraved pump panel tags shall be utilized for each instrument and control. All panel mounted instruction plates shall be mechanically attached.
CFM metering valve CAFS air metering valve
Solution Metering valve CAFS solution metering valve

14. Testing Requirements

The completed unit shall undergo a manufacturer's run-in test prior to delivery. The engine, pump and air compressor shall be operated at full load for a minimum period of two (2) hours, during which time the test operator shall monitor and record the functions and performance of each system component. Compressed air foam shall be produced during the test.

This testing shall be performed to ensure proper system operation and performance prior to shipment. The manufacturer shall provide written certifications that the tested unit meets all performance criteria contained herein. Water flow performance shall be measured using standard Fire Department test methods. Air flow performance shall be measured with a temperature and pressure compensated air flow meter

15. Manuals

Two (2) copies of operation and maintenance manuals shall be provided to the purchaser with each unit. These manuals shall include detailed instructions in the operation and maintenance of the overall unit, engine, water pump, air compressor, and foam proportioner.

16. Warranty
ENGINE --- 1 yr. *
COMPRESSOR--- 1 yr. *
WATER PUMP---1 yr. *
PROPORTIONER ---1 yr. *
WATER TANK--- Lifetime *
ROBWEN --- All fabrication and materials are warranted for a period of two years, barring accidents, abuse or negligence. Excluded from warranty are all consumables and parts subject to routine replacement. Robwen will repair or assist in getting repaired the product in entirety.
* Covered by the original manufacturers warranty.